.Skip to main content

Powerbox 13.8VDC Power Supply with Battery Charging - AC Fail and Low Battery Monitoring

Powerbox

$205.92 - $517.44
(No reviews yet) Write a Review
SKU:
STK PBB2561210CML PBB2S1335 PB
UPC:
2998826747395
Adding to cart… The item has been added

Available Variants: Amperage - 10, 3.5, 7

The PB256 Series is a family of 13.8Vdc, 110W / 140W off-line battery chargers / DC uninterruptable power supplies which operate from 220/240Vac mains power. when connected to a lead-acid battery. These units provide uninterrupted power to a DC load in the event of mains failure.

The PB256 Series contains a two-step current limited float charger, battery charge current limiting, a battery low voltage disconnect and mains/charger and battery alarms. It employs high efficiency technology, combined with very low output noise that makes it suitable for powering broad range of loads such as communication equipment, control equipment and alarm systems etc.

The PB256 is available in chasis mount enclosure, and can be fitted into the WMBB wall mount box. A supplementary heatsink is needed for 140W models to operate at maximum power. All models employ natural convection cooling.

  • 138W 12VDC.
  • Battery Backup System.
  • DC UPS Connectable.
  • Independent Load and Battery Current Limited.
  • Converter ON/OK alarm.
  • Battery Low Alarm.
  • Battery low voltage disconnect switch with internal electronic circuit breaker.
  • Battery Over Load protection.
  • Conformal Coating option for wet areas.
  • C-Tick Approved.
Input
Input Voltage 190-.264Vac, or 190-.400Vdc
Frequency 45 to 65 Hz
Input Current 3A maximum
Inrush current 15A on cold start
Line Regulation 0.2% typical
Output
Output Voltage 13.8Vdc
Output Power 138W, See power derating curve
Output Current 13.8Vdc: 10A
Load regulation 2% typical
Ripple & Noise 25 mVp-p (13.8Vdc output)
Efficiency > 80%
Protection
Current limit type
(Load circuit)
Constant current > LVD volts
Foldback & hiccup < LVD volts
Short circuit protection Indefinite, auto-resetting
Over-voltage protection 15.5 to 19.5 V latching (13.8Vdc output)
Reverse polarity protection Internal fuse
Isolation

Input to Output: 2.1Kvdc 1 min

Output to Ground: 2.1Kvdc 1 min

Output to Ground: 700Vdc 1 min

Environmental
Operating temperature

0 to 50°C ambient

For derating, see curve in technical illustrations

Humidity 5 to 90% relative humidity (non-condensing)
Over-temperature protection Automatic & auto-resetting
Cooling requirement Natural convection
Shock/Impact 50G 11mS once each along x, y and z axis
Alarm and Battery Functions
Converter ON/OK alarm Indicated by voltage-free changeover relay contacts & green LED: ON=OK
Battery low alarm <11.3Vdc: 12V Battery
Indicated by voltage-free changeover relay contacts & green LED: ON=OK.
Low voltage disconnect

10.8V (Typical for 12Vdc battery)

Battery over-load

protection

Electronic circuit breakerauto-reset
Battery to load voltage drop 0.2 V (27.6V output)
Optional Features
Battery Charge Limit

Option BCL: Specify battery charge current based on battery size.

Heatsink Option H: Supplementary heatsink
Conformal Coating Option CC: Tropic protection for moist areas
Standards and Approvals
C-Tick AS/NZS CISPR11 Group 1 Class A.
Safety Compliles with AS/NZS 60950, Class 1
EMC Emissions comply with AS/NZS CISPR11,
Group 1, Class B. Complies with ACA EMC
Scheme, C-Tick
Mechanical
Input Connector

AC Mains 10A Class 1

IEC60320 power inlet

Load and Battery

Connector

4 way pluggable screw terminal block.

Suitable for up to 1.5mm² wire

Alarms Connector

6 way pluggable screw terminal block

Suitable for up to 1.5mm² wire

Case size 230 L x 93 W x 46 H (mm)
Weight 850g
Finish: Silver
Power Output: 10 A at 13.8 Vdc
Battery Backup: Yes
Battery Leads Included: No
Fused Outputs: No
LED Indicators: Yes
Lockable Metal Enclosure: No